FIRE PRE-INSPECTION - 14702 KATHY ST. WESTMINSTER

RCCS · Fire Pre-Inspection Field Tool

14702 Kathy St.
Fire Clearance Readiness Checklist

Use this tool during the September 10, 2026 fire pre-inspection to review the property room-by-room, door-by-door, alarm-by-alarm and evacuation-route-by-evacuation-route before the next official OCFA fire-clearance inspection.

Facility 14702 Kathy St.
City Westminster, CA 92683
Planned Capacity 6 Clients
Proposed Configuration 3 A · 2 NA · 1 Bedridden
Inspection Progress 0 / 0 complete

DO NOT LABEL THE PROPERTY “READY” WHILE A CRITICAL ITEM REMAINS UNRESOLVED

This pre-inspection should evaluate the home as it will actually operate: furnished rooms, resident mobility equipment, normal locked-door conditions and the proposed ambulatory, non-ambulatory and bedridden resident configuration.

Priority 0 · Previous OCFA Corrections

1. Verify Every Previously Cited Deficiency

These are specific deficiencies previously documented at this property.

Bedroom #5 Exterior Door — City Approval & Final Documentation

OCFA previously cited the exterior door added to Bedroom #5 and requested approved plans and paperwork from the City Building Department.

Required inspection check
  • Confirm a building permit was obtained for the added exterior door.
  • Confirm required City inspections were completed.
  • Confirm final approval/final inspection status.
  • Confirm the finished installation matches the approved plan.
  • Have permit documents and final approval available for review.
RCCS safer preparation

Photograph the permit, approved plan and final inspection documentation. Do not rely only on an application receipt or verbal statement that the permit exists.

Correct CO Alarm Coverage for Bedroom Hallways

The previous inspection specifically called for CO detection in the hallway serving Bedrooms #4–#5 and the hallway serving Bedrooms #1–#3.

Verify
  • CO alarm present in hall serving Bedrooms #1, #2 and #3.
  • CO alarm present in hall serving Bedrooms #4 and #5.
  • Devices function.
  • Required devices interconnect correctly.
  • Hardwired with battery backup where required.
  • Listed / approved device.
Safer installation recommendation

Do not automatically mount a CO alarm at five feet, near the floor or near the ceiling. CO alarms have model-specific mounting instructions. Verify the exact manufacturer instructions for every device.

If it is a combination Smoke/CO alarm, its location must also meet the smoke-alarm placement limitations.

Evacuation Maps Corrected

Verify the posted plan shows
  • Bedridden resident room.
  • Non-ambulatory resident rooms.
  • Correct direction of travel for each evacuation route.
  • Exterior exits.
  • How occupants identify the fire alarm.
  • “In case of emergency, dial 9-1-1.”
Field verification

Stand in each resident bedroom and physically follow the route shown on the posted map. The arrows should correspond to the actual route being relied upon for that resident.

Exit Door Locks — Single-Action Correction

The previous property-specific inspection instructed that exit door locks be replaced so they operate as a single action.

Test every required exit and egress gate
  • No key required from the egress side.
  • No tool required.
  • No unusual sequence or special knowledge.
  • No prohibited manual slide bolt.
  • No prohibited flush bolt.
  • No padlock obstructing required egress.
  • Door releases during normal opening operation.
Safest approach

Because this property has already been specifically cited regarding its locking arrangement, treat the prior correction as the target configuration rather than attempting to rely on a less protective arrangement.

Priority 0 · Actual Operating Configuration

2. Occupant Configuration & Furnished-Room Review

Inspect the home as it will actually operate after residents move in.

Floor Plan Matches Proposed Resident Use

Verify the plan identifies
  • Every room and its intended use.
  • All resident bedrooms.
  • Resident count per bedroom.
  • Ambulatory status.
  • Exterior exits.
  • Door clear widths.
  • Client hallway widths.
  • Smoke alarm locations.
  • CO alarm locations.
  • Exit routes to the public way.
  • Gate opening widths.

Bedrooms Furnished for Intended Capacity

Inspect with normal furnishings present
  • All planned beds.
  • Dressers.
  • Nightstands.
  • Resident storage.
  • Chairs.
  • Wheelchairs.
  • Walkers.
  • Other expected mobility equipment.
Do not stage a temporary inspection-only pathway

The usable evacuation route should remain available after the resident and normal furniture are actually in place.

Wheelchair / Emergency Gurney Maneuverability

Practical field simulation

Move an actual wheelchair through each route used by a non-ambulatory resident.

  • Bedroom doorway.
  • Hallway.
  • Turns.
  • Common area.
  • Exterior door.
  • Landing.
  • Ramp if present.
  • Side yard.
  • Gate.
  • Public way.

Also consider whether emergency personnel could reasonably maneuver a stretcher/gurney through the same physical path.

Priority 0 · Room-by-Room

3. Client Bedroom Configuration Matrix

Record the actual resident status, capacity and evacuation configuration.

Room Resident Status # Residents Exit Configuration Clear Exit Width Notes
Priority 0 · Life Safety

4. Smoke Alarms — Coverage, Placement & Testing

Review the entire habitable portion of the home, not only resident bedrooms.

Required Habitable Areas Have Smoke Alarms

Verify coverage including
  • Every bedroom.
  • Living room.
  • Dining room.
  • Hallways.
  • Foyer / entry areas as applicable.
  • Basement if applicable.
  • Other similar habitable spaces.

Do not install ordinary smoke alarms directly in kitchens, bathrooms, closets or garages unless a specifically applicable listed design requires otherwise.

Correct Alarm Type & System Configuration

  • Properly listed smoke alarm.
  • California State Fire Marshal approved/listed.
  • Hardwired where required.
  • Battery backup present.
  • Required smoke alarms interconnected.
  • Activation of one causes interconnected alarms to sound.
  • Alarm audible throughout sleeping areas.
  • Replace failed devices.
  • Replace devices beyond permitted service life.
  • Replace where device age/date cannot be verified if required.
Safer replacement selection

If replacing equipment, use current-production listed devices from a major manufacturer. Near cooking areas, use an appropriately listed nuisance-resistant/photoelectric alarm where permitted by the actual installation conditions.

Smoke Alarm Ceiling / Wall Position

Conservative installation guidance
  • Always follow the exact manufacturer's instructions for the model.
  • Ceiling mounting is generally preferred where allowed.
  • Near the center of a flat ceiling is preferable where practical.
  • Avoid the dead-air area at the exact wall/ceiling corner.
  • A commonly used installation guideline for ceiling-mounted alarms is at least 4 inches from the wall.
  • When the manufacturer permits wall mounting, many models place the top of the alarm approximately 4 to 12 inches below the ceiling.

Do not use “6 inches from the wall” as a universal rule. The listing and manufacturer's instructions for the actual device control its permitted mounting position.

Distance From Cooking Appliances

Standard cooking separation 10 ft

Do not place a normal smoke alarm within the applicable cooking-appliance exclusion area unless the device is specifically listed for the closer location.

Near-kitchen area 10–20 ft

Where applicable, use appropriate nuisance-resistant detection technology or an approved alarm-silencing feature.

Safer recommendation

If a sleeping-area hallway is close to the kitchen, do not simply remove the required alarm. Use an appropriately listed alarm type and position it according to the device instructions and applicable separation requirements.

Steam / HVAC / Ceiling-Fan Interference

Tub/Shower Bathroom Door 36 in.
HVAC Supply 36 in.
Ceiling Fan Tip 36 in.
Cooking Zone 10 ft.
Safer placement review
  • Avoid direct forced-air supply airflow.
  • Avoid strong drafts from windows or exterior doors.
  • Avoid steam-heavy placement adjacent to a tub/shower bathroom.
  • Maintain appropriate separation from ceiling fan blade tips.
  • Follow the exact alarm listing if the physical room configuration prevents standard separation.

Full Interconnection & Audibility Test

Field test
  1. Close all bedroom doors.
  2. Activate one smoke alarm using its test function.
  3. Verify required interconnected alarms sound.
  4. Stand in each sleeping room with its door closed.
  5. Confirm the alarm is clearly audible.
  6. Test additional alarms if any device or area is questionable.
Priority 0 · Life Safety

5. Carbon Monoxide Alarms

Correct Required Locations

Verify detection
  • In the area leading to each separate sleeping area.
  • On each occupiable level where required.
  • In bedrooms where a fireplace or fuel-burning appliance triggers an additional bedroom-location requirement.
Mount according to the exact device instructions

Carbon monoxide does not require one universal mounting height. The manufacturer may permit wall, ceiling or plug-in installation depending on the listed product.

CO Device Specifications & Interconnection

  • Residential CO alarm properly listed.
  • California approved/listed where required.
  • Hardwired where required.
  • Battery backup where required.
  • Required CO devices interconnected.
  • No fault indication.
  • No end-of-life warning.
Safer installation practice

Keep the device unobstructed and follow manufacturer separation instructions from furnaces, fireplaces, water heaters, vents, windows and exterior doors.

Perform CO Alarm Test

  1. Use the manufacturer's Test/Reset function.
  2. Verify the device completes its normal test sequence.
  3. Verify required interconnected devices respond.
  4. Check for trouble or end-of-life indications.
Priority 0 · Egress

6. General Exits, Hallways & Path to the Street

Exit Clear Width 32 in. min.
Exit Door Height 6'8" min.
Client Hallway 36 in. min.
General Exits 2 remote

Two Remotely Located Approved Exits

Confirm the dwelling has at least two approved exit routes that are remotely located from one another.

Measure the Actual Clear Door Opening

  • Minimum clear opening: 32 inches.
  • Measure with the door open to 90 degrees.
  • Client-serving exterior exit height: 6 feet 8 inches.
  • Sliding doors must provide the required unobstructed clear opening.
Measurement method

Measure the actual usable space between the face of the opened door and the opposite stop/frame. Do not use the nominal advertised door size.

Client Hallways Maintain Required Width

Measure the narrowest usable hallway location after furniture and equipment are in their intended positions.

Target minimum: 36 inches in client-serving hallways.

Safer operating margin

Where practical, maintain more than the exact minimum so moved furniture, carts or mobility equipment do not reduce the effective evacuation width.

Exit Path Clear All the Way to the Public Way

  • No furniture in the required route.
  • No stored wheelchair blocking the route.
  • No boxes or facility supplies.
  • No trash cans obstructing side-yard travel.
  • No patio furniture narrowing the path.
  • No inaccessible locked gate.
  • No vehicle blocking the route.
  • Measure the narrowest exterior portion.

Common-Area Egress Route

  • Review how many intervening spaces are crossed before reaching the exterior.
  • Do not rely on a required egress path through a storeroom.
  • Do not rely on a required egress path through a closet.
  • Do not rely on a required egress path through the garage.
  • Review separated-kitchen conditions carefully.
Priority 0 · Non-Ambulatory

7. Non-Ambulatory Client Bedroom Exiting

Each Non-Ambulatory Bedroom Has an Accepted Exit Configuration

Accepted configurations
  1. Bedroom → Exterior.
  2. Bedroom → Adjacent Bedroom → Exterior.
  3. Bedroom → Hallway → Exterior.
  4. Bedroom → Hallway → Another Client Bedroom → Exterior.
Safer layout preference

When the home layout allows it, direct bedroom-to-exterior exiting minimizes turns and intervening rooms and creates the simplest evacuation route.

Hallway Separation Where Hallway Is Part of Resident Egress

  • Review required separation from living, dining, kitchen, foyer and similar areas.
  • Required separation doorway uses appropriate solid-door construction.
  • Verify minimum 1-3/8 inch solid wood construction where required.
  • Verify self-closing or smoke-activated automatic-closing function.
Door-closing test

Open the door fully and release it. Confirm it closes completely rather than stopping before the closed position.

Priority 0 · Bedridden Client

8. Bedridden Client Bedroom

Perform a separate mini-inspection of the proposed bedridden bedroom.

Bedridden Room Located on First Story

Confirm the proposed bedridden client's sleeping room is on the first story.

Unsprinklered Bedridden Configuration

  • Confirm permitted number of bedridden clients.
  • Direct exterior exit available where required.
  • Exterior exit provides at least 32 inches clear width.
  • Required interior and exterior operation of the exterior door.

Bedridden Room Door Construction

  • Required solid wood door construction verified.
  • Verify 1-3/8 inch solid wood where applicable.
  • Required smoke gasketing installed.
  • Door self-closes or automatically closes as required.

No Problematic Locking Hardware on Interior Bedroom Door

Review the interior door for deadbolts, night latches, security chains or similar hardware that could conflict with the required bedridden-room arrangement.

Bed-to-Exterior Evacuation Simulation

Practical test

Evaluate whether caregivers could evacuate a resident who provides no physical assistance without first moving furniture or stored equipment.

Priority 1

9. Fire Sprinkler Status

Determine Whether the Home Is Sprinklered

Review occupancy-dependent sprinkler requirements
  • Number of bedridden clients.
  • Location of non-ambulatory residents by story.
  • Whether any client rooms are proposed on upper floors.
Visual sprinkler inspection

If the home has sprinklers, visually check for painted, covered, damaged or obviously obstructed sprinkler heads. Formal testing, repairs and system modifications should be performed by qualified fire-protection personnel.

Priority 1

10. Emergency Escape / Rescue Openings

Bedroom Rescue Openings Are Operable

  • Opening actually opens.
  • No key required from inside.
  • No tool required.
  • No special knowledge required.
  • No furniture blocks operation.
  • Exterior remains accessible to firefighters.
  • Bars / grilles release appropriately where present.
Field test

Physically open every applicable rescue window/opening fully rather than visually assuming it works.

Priority 1

11. Attached Garage / Dwelling Separation

Garage-to-Dwelling Door

  • Door in good condition.
  • Door self-closes.
  • Door positively latches.
  • Required solid wood / steel / rated construction verified.
  • Smoke gasket where applicable.
Functional test

Open the door fully and release it. Confirm the closer brings it fully closed and that it positively latches.

No Unapproved Openings in Garage Separation

  • No dog door.
  • No improper window/opening into a sleeping room.
  • No unsealed penetration.
  • No unapproved garage living/sleeping use.
Priority 1

12. Fire Extinguisher

Minimum Rating 2A:10B:C
Top of Unit ≤ 5 ft.
Bottom ≥ 4 in.
Service / Proof Current

Correct Extinguisher & Mounting

  • Minimum 2A:10B:C rating.
  • Wall mounted.
  • Visible.
  • Readily accessible.
  • Top no more than five feet above floor.
  • Bottom at least four inches above floor.
  • Current annual service tag or acceptable recent purchase proof.
  • No obvious damage or discharge.
Priority 2

13. Water Heater & Other Ignition Sources

Combustible Storage Cleared

Maintain required combustible clearances around the water heater, furnace and other ignition sources based on the equipment and its listed installation requirements.

Safer housekeeping practice

Avoid using the immediate water-heater or furnace area as general facility storage even where an item appears to technically fit.

Priority 1 · Mobility

14. Thresholds, Elevation Changes, Ramps & Stairs

Thresholds & Floor Elevation Changes

  • Review small changes in level for required beveling.
  • Review larger changes in elevation for required ramp treatment.
Pay special attention to Bedroom #5

Evaluate the new exterior door threshold, exterior landing and grade. A 32-inch-wide door is not practically useful for a non-ambulatory evacuation if a wheelchair cannot safely cross the threshold or landing.

Existing Stairs — If Applicable

  • Check rise.
  • Check tread/run.
  • Check usable stair width.
  • Identify spiral or winding stair conditions.
Priority 2

15. Address Identification

14702 Clearly Visible From the Street

  • Minimum four-inch-high numbers.
  • Strong contrast against background.
  • Attached to the structure.
  • Clearly visible from street approach.
Priority 0 · Documentation

16. Inspector-Ready Document Packet

Updated Fire Clearance / Licensing Documentation Available

Updated Site Plan Available

Updated Floor Plan Available

Bedroom #5 City Permit / Final Approval Documents Available

Fire Extinguisher Service / Purchase Documentation Available

Smoke & CO Alarm Manufacturer / Model Information Available

Photograph the model labels. Keep the installation manual for each alarm model available so placement, mounting method, power source and replacement age can be verified.

Current Evacuation Maps Printed & Posted

Final Gate

17. Conduct a Full Mock Fire Inspection Before Leaving

Lock Every Exit as It Would Normally Be Locked

Start from inside and verify the required door and gate can be opened without a prohibited key, tool or sequence.

Activate Smoke Alarm & Verify Whole-Home Response

Test CO Alarm System

Walk Every Client Evacuation Route

Repeat Non-Ambulatory Route With a Wheelchair

Evaluate Bedridden Evacuation From Bed to Exterior

Photograph Critical Measurements & Corrections

18. Client Action Summary

Record corrections that should be completed before the next official fire-clearance inspection.

19. Pre-Inspection Review